APOLLO GROUP CO., LTD.

AP990 40 – 120 kVA (3:3)

Characteristics Technical Specifications Documents
  • Advanced dual-core DSP control technology, rectification and inversion are controlled by dual DSP
  • Output power factor 1.0, load capacity improved 11% more than traditional products
  • Active Power Factor Correction Technology, input power factor up to 0.99
  • System efficiency improved to 96%, energy saving rate is doubled
  • Working efficiency up to 99% in ECO mode
  • Dual input design, supporting independent bypass
  • Advanced digital and parallel technology, providing higher reliability than single system
  • Wide input voltage range, 50 / 60 Hz auto-sensing frequency
  • 50 Hz / 60 Hz frequency conversion mode
  • Compact internal layout, small footprint
  • Fan speed varies intelligently with temperature, reducing noise and extending its service life
  • Features strong fault tolerance, one fan damaged takes 50% of the load, two fans damaged take 30% of the load
  • Conformalcoating technology to make UPS operate in harsh environment for a long time
  • Effective hardware and software protection, robust self-diagnosis function, abundant event log for future check
  • Linear downgrading in low voltage input reducing battery discharging times
  • Flexible battery configuration setting, selectable battery numbers: 30 ~ 46 pcs
  • Ability to switch on the UPS by battery in the absence of mains power (Cold start)
  • Zero switching time for UPS power supply mode when the mains power is unstable, ensuring the output is uninterrupted
  • Settable delayed start time when mains power is restored
  • 5 inches LCD colorful touch screen, friendly human & machine interface
  • Powerful background software for parameters configuration andonline upgrade
  • Advanced multi-platform communication for UPS monitoring: RS232, USB, RS485, NET, dry contacts, SNMP card, Wi-Fi card and GPRS card
  • Intelligent battery management, automatic equalized and float charging control, charger dormancy control, improving the reliability of charger and extending the battery life
  • Options and accessories: supplied RS232, USB, RS485, NET, parallel, LBS, dry contacts, EPO and battery temperature            compensation interface; optional SNMP card, Wi-Fi card, GPRS card, battery temperatur sensor, EMD detector and SMS alarms

Model

AP9940

AP9960

AP9980

AP99100

AP99120

Capacity

40 kVA / 40 kW

60 kVA / 60 kW

80 kVA / 80 kW

100 kVA / 100 kW

120 kVA / 120 kW

INPUT

Input wiring

Three-phase   five-wire (3Φ + N + PE)

Rated voltage

380 / 400 / 415   Vac

Voltage range

304 ~ 485 Vac   (no downgrading), 138 ~ 304 Vac (linear downgrading between 40% ~ 100% load)

Rated frequency

50 / 60 Hz   (auto-sensing)

Frequency range

40 ~ 70 Hz

Power factor

≥ 0.99

Bypass voltage range

-60% ~ +20%   (settable)

Total harmonic distortion (THDi)

≤ 3%

OUTPUT

Output wiring

Three-phase   five-wire (3Φ + N + PE)

Rated voltage

380 / 400 / 415   Vac

Voltage   regulation 

±1%

Frequency

Synchronized   with utility in mains mode, 50 / 60 Hz ±   0.1% in battery mode

Waveform

Sinusoidal

Power factor

1

Total harmonic distortion (THDv)

≤ 1% (linear   load);  ≤ 4% (non-linear   load)

Crest factor

3:1

Overload

105% ~ 110% for 60 min, 110% ~ 125% for 10 min,   125% ~ 150% for 1 min, > 150% for 0.2 s

BATTERIES

DC voltage

± 192 Vdc (± 180 ~ ± 264 Vdc settable)

40 kVA built-in battery: ± 240 Vdc (80 pcs 9 Ah/12 V)

Number of battery

32 pcs (30 ~ 44 pcs settable)

Charging current (max.)

12   A

24   A

36 A

Recharge time

Depend   on the capacity of battery

SYSTEM

Efficiency

Max. 96% in   online mode, 99% in ECO mode

Transfer time

0 ms

Protections

Short-circuit, overload, overtemperature, excessive low battery, overvoltage, undervoltage, fans failure

Max. number of parallel connections

4

Communications

Standard configuration: RS232, USB, RS485, NET, dry contacts;

Optional configuration: SNMP card, Wi-Fi card, GPRS card

Display

5 inches colorful LCD touch screen

OTHERS

Operating temperature

0℃ ~ 40℃

Storage temperature

-25℃ ~ 55℃ (without battery)

Relative humidity

0% ~ 95%   (non-condensing)

Altitude

≤ 1000 m; above   1000 m, downgrading 1% for each additional 100 m

IP rating

IP 20

Noise level at 1   m

≤ 65 dB

Dimensions (W ×   D × H) (mm)

360 × 850 × 885

360 × 850 × 950

360 × 850 × 1200

440 × 850 × 1200

Packaged   dimensions (W × D × H) (mm)

450 × 940 × 1055

450 × 940 × 1120

450 × 940 × 1370

530 × 940 × 1370

Net weight (kg)

95,

295 (built-in   BAT)

130.5

156

198

Gross weight (kg)

110,

310 (built-in BAT)

145

172

218.5