APOLLO GROUP CO., LTD.

AP890 80 – 120 kVA (440V/480V)

Characteristics Technical Specifications Documents

● Online double-conversion with full DSP control

● IGBT inverter with output isolation transformer

● 100% unbalance load capability

● Output power factor 0.9

● Generator compatible

● Support battery cold start and mains supply self-starting

 ECO mode operation for energy saving

● Perfect protective function

● 5.7 inches LCD touch screen, friendly human & machine interface

● Front access makes maintenance and replacement easy

● Intelligent self diagnose function, all kinds of fault protection, large capability of history record storage

● High MTBF (> 200,000 h)

 Low MTTR (< 0.5 h)

● Standard emergency power off (EPO)

● Standard RS232, RS485, dry contacts communication port

● Optional SNMP communication port

● Optional N+X redundancy parallel up to 6 units

MODEL

AP8980

AP89100

AP89120

Capacity

80 kVA / 72 kW

100 kVA / 90 kW

120 kVA / 108 kW

INPUT

Rated   voltage

440 V / 480 V

Voltage range

+15% / -20%

Rated frequency

60 Hz

Frequency range

60 Hz ± 10%

Power factor

≥ 0.95 (APF)

Current Distortion

8% (APF)

Bypass voltage range

± 20% (settable)

ECO voltage range

± 10% (settable)

Input current   limiting

1.25 ( settable 0.1 - 1.25)

OUTPUT

Rated voltage

440 / 480 Vac

Voltage regulation

± 1%

Frequency

Synchronized with   utility in AC mode; 60 Hz ± 0.1% in battery mode

Waveform

Sinusoidal

Crest factor

3:1

Total   harmonic distortion(THDV)

≤   2% (linear load); ≤ 5% (non-linear load) 

Transfer time

AC mode to Battery mode: 0   ms

Inverter model to Bypass   mode: 0 ms

ECO mode to Inverter mode:   max. 10 ms 

Inverter   overload capability

105%:   long time running, 105% ~ 110% for 1 h, 110% ~ 125% for 10 min,

125%   ~ 150% for 1 min, 150% ~ 200% for 200 ms, > 200% for 100 ms

Bypass   overload capability

≤ 150%: long time running

150% < load < 200%: shutdown   in 1 min

> 200%: shutdown in 100   ms

BATTERIES

 

DC voltage

360 V (28 pcs ~ 32 pcs settable)

Inbuilt   battery of standard model

External battery

Charger current

0.1 C (settable 0.1 - 0.25 C)

SYSTEM

 

Efficiency

Operation mode ≥ 92%; ECO   mode ≥ 97%

Alarm

Battery mode, low battery, fans fault etc.

Communications

RS232 / RS485 / dry contacts (standard), SNMP (optional)

Surge protection

IEC60664-1

Insulation resistance

> 2 MΩ (500 Vdc)

Dielectric strength

2820 Vdc, No arc in 1min

IP rating

IP 20

EMI

EN62040-2

EMS

IEC61000-4-2 (ESD)

IEC61000-4-3 (RS)

IEC61000-4-4 (EFT)

IEC61000-4-5 (surge)

OTHERS

 

Humidity

0 ~ 95% RH @ 0 ~ 40 (non-condensing)

Noise   Level

65 dB

Dimensions (W × D × H) (mm)

700 × 800 × 1700

Packaged dimensions (W × D × H)   (mm)

800 × 900 × 1950

Net   / Gross weight (kg)

590   / 620

630   / 660

690   / 720