APOLLO GROUP CO., LTD.

AP200R 600 – 2000 VA

Characteristics Technical Specifications Documents

Microprocessor-based digital control

Boost and buck AVR for voltage stabilization

Auto sensing frequency

Wide input voltage range

Power-on self test

Cold start

Auto restart when mains power is restored

Auto track mains phase to ensure that inverter output voltage has same phase with utility voltage, reducing transfer time and peak surge

Intelligent battery management: battery temperature compensation to extend the battery life; three-stage charging to shorten recharge time

Short circuit, battery overcharge / overdischarge, overload, surge protections

Automatic charging in OFF mode

Optional no-load shutdown

Optional RS232 / USB communication port and RJ11 / RJ45 protection

Unattended safety shutdown: system alarm and auto Power-On / Off by RS232 or USB interface communicating with PC

MODEL AP260R AP280R AP2120R AP2150R AP2200R
Capacity

600 VA

360 W

800 VA

480 W
1200 VA 720 W

2000 VA

1200 W

2000 VA

1200 W
INPUT
Voltage

100 / 110 / 120 V: 80 ~ 150 Vac;

220 / 230 / 240 V: 162 ~ 295 Vac (145 ~ 295 Vac optional)

Frequency 50 / 60 Hz ± 10% (auto-sensing)
OUTPUT
Voltage 100 / 110 / 120 Vac ± 10% or 220 / 230 / 240 Vac ± 10%
Frequency 50 / 60 Hz ± 1% (auto-sensing)
Waveform Mains mode: pure sine wave; Battery mode: simulated sine wave
Transfer time Typical 2 ~ 7 ms, 10 ms max.
BATTERIES
DC voltage 12 V 24 V
Configuration 12 V / 7.0 Ah × 1 12 V / 8.0 Ah × 1 12 V / 7.0 Ah × 2 12 V / 8.0 Ah × 2 12 V / 9.0 Ah × 2
Recharge time 6 ~ 8 h
OTHERS
Protections Short circuit - battery overcharge – overdischarge – overload - surge
Communications USB / RS232 / SNMP (optional)
Humidity 20 ~ 90% RH @ 0 ~ 40℃ (non-condensing)
Noise level ≤ 45 dB (1 m)
Rack mount Net / Gross weight (kg) 7.0 / 7.5 8.2 / 8.7 11.6 / 12.1 13.3 / 13.8 14.9 / 15.4

Dimensions

(W × D × H) (mm)
308 × 438 × 88 308 × 438 × 132

Packaged dimensions

(W × D × H) (mm)
395 × 525 × 185 395 × 525 × 225